BLDUP | The CRE Database

Permit MOD202100016 at 3101 Park Center Drive, Alexandria, VA, 22302

Issue Date
05/21/21

Type
Permit

Docnumber
MOD202100016

Neighborhood
John Adams

Consideration Amount
$10,000.00

Description

Code modification to resolve condition where existing storm water lines are passing over the stair pressurization duct in the corridor. If a fire rated shaft was built the duct would need to be lowered out of the path of the existing storm water lines. Many other MEPF systems run through the corridor so by lowering the duct the ceiling would also be lowered to approx. 7'. With the use of the 3M 615+ duct wrap the duct can remain close to the existing storm water line and the ceiling does not ...Code modification to resolve condition where existing storm water lines are passing over the stair pressurization duct in the corridor. If a fire rated shaft was built the duct would need to be lowered out of the path of the existing storm water lines. Many other MEPF systems run through the corridor so by lowering the duct the ceiling would also be lowered to approx. 7'. With the use of the 3M 615+ duct wrap the duct can remain close to the existing storm water line and the ceiling does not need to be lowered to approx. 7'.
Read More >>Read Less <<

Ownership

Applicant


(113) Related Documents at 3101 Park Center Drive

To view Related Documents you have to be a FREE BLDUP member.

View All 113 Related Document(s)

Can't Find What You're Looking For?