3755 Monte Villa Parkway Overview

Permitted Construction:

BLDUP Latest Activity

A permit for the amount of was issued on 02/05/24 to Ownership.

Permit Details: E24-04007 ION Q 1st Floor Lab T.I. MODIFICATION TO EXISTING TYPE II-A, 3-STORY BUILDING. CEILINGS & WALLS RENOVATED TO CREATE NEW LABORATORY (OH2), CORRIDOR (LH) & MAINTENANCE (OH1) SPACES. 8,873 SQ.FT OF AFFECTED AREA. EXISTING PENDENT SPRINKLERS REMOVED & REPLACED, EXISTING OUTLETS RE-USED WHEREEVER POSSIBLE. MECH TEES USED WHERE EXISTING OUTLETS AREN'T SUFFICIENT FOR COVERAGE. NEW EXTENDED COVERAGE CONCEALED PENDENTS INSTALLED ON FLEXES IN LAB#3, WHILE NEW EXTENDED COVERAGE CONCEALED PENDENTS IN LAB #2 TO BE INSTALLED ON HARD-PIPE DROPS. NEW STANDARD COVERAGE CONCEALED PENDENTS INSTALLED ON FLEXES EVERYWHERE ELSE. TO ACHIEVE APPROPRIATE HYDRAULIC CALC SAFETY FACTOR OF 10% OR 10 PSI (WHICHEVER IS LARGER), SELECT BRANCHLINES ARE TO BE UPSIZED AND GRIDDED TOGETHER W/ NEW GRV SCH 10 PIPE. Total heads = 61